INSTALLATION COMMISSIONING FORM

INTABLOC HEAT PUMP

The below settings are recommended parameter settings for the Intabloc heat pump range. Please check the below settings when turning on your heat pump to commission your system.

PARAMETER SETTINGS
To access parameter settings; Press both Mode[D8] & Up▲[D4] key together for 5 seconds. Press Down▼[D3] and Up▲[D4] key to scroll parameters. Press Confirm[D6] to select parameter. Press Down▼[D3] or Up▲[D4] to edit parameter value. Press Confirm[D6] to save parameter setting. Once finished editing parameters; press Power[D10] to exit and return to home screen.
PARAMETER:[P00] RANGE: [0]=Off [1]=On RECOMMENDED SETTING: [8kW=1] [11kW=1] [16kW=1] [17kW=1] [25kW=1] [30kW=1]
PARAMETER:[P01] RANGE: 2 ~ 15⁰C RECOMMENDED SETTING:[8kW=2⁰C] [11kW=2⁰C] [16kW=2⁰C] [17kW=2⁰C] [25kW=2⁰C] [30kW=2⁰C]
PARAMETER:[P02] RANGE: 2 ~ 15⁰C RECOMMENDED SETTING:[8kW=2⁰C] [11kW=2⁰C] [16kW=2⁰C] [17kW=2⁰C] [25kW=2⁰C] [30kW=2⁰C]
PARAMETER: [P03] RANGE: -20 ~ 5⁰C RECOMMENDED SETTING:[8kW=0⁰C] [11kW=0⁰C] [16kW=0⁰C] [17kW=0⁰C] [25kW=0⁰C] [30kW=0⁰C]
PARAMETER: [P06] RANGE: 10 ~ 35⁰C RECOMMENDED SETTING: [8kW=30⁰C] [11kW=30⁰C] [16kW=30⁰C] [17kW=30⁰C] [25kW=30⁰C] [30kW=30⁰C]
PARAMETER: [P07] RANGE: 15 ~ 99 RECOMMENDED SETTING: [8kW=15] [11kW=15] [16kW=15] [17kW=15] [25kW=15] [30kW=15]
PARAMETER: [P08] RANGE: 15 ~ 99 min RECOMMENDED SETTING: [8kW=35] [11kW=35] [16kW=35] [17kW=35] [25kW=35] [30kW=35]
PARAMETER: [P11] RANGE: 2 ~ 10 RECOMMENDED SETTING: [8kW=10] [11kW=10] [16kW=10] [17kW=10] [25kW=10] [30kW=10]
PARAMETER: [P13] RANGE: [0]= No Defrost [1-4]=Defrost multi interval RECOMMENDED SETTING: [8kW=1] [11kW=1] [16kW=1] [17kW=1] [25kW=1] [30kW=1]
PARAMETER: [P15] RANGE: 0 ~ 65⁰C RECOMMENDED SETTING: Refer to manual
PARAMETER: [P16] RANGE: 0 ~ 65⁰C RECOMMENDED SETTING: Refer to manual
PARAMETER: [P17] RANGE: 0 ~ 65⁰C RECOMMENDED SETTING: Refer to manual
PARAMETER: [P18] RANGE: 0 ~ 65⁰C RECOMMENDED SETTING: Refer to manual
PARAMETER: [P21] RANGE: 50 ~ 240 deg RECOMMENDED SETTING:[8kW=180] [11kW=200] [16kW=180] [17kW=160] [25kW=180] [30kW= ]
PARAMETER: [P22] RANGE: 50 ~ 240 deg RECOMMENDED SETTING:[8kW=150] [11kW=180] [16kW=150] [17kW=170] [25kW=180] [30kW= ]
PARAMETER: [P23] RANGE: [0]=No [1]=Check [2]=Manual [3]=Auto RECOMMENDED SETTING:[8kW=3] [11kW=3] [16kW=3] [17kW=3] [25kW=3] [30kW=3]
PARAMETER: [P24] RANGE: -5 ~ 10⁰C RECOMMENDED SETTING:[8kW=3⁰C] [11kW=1⁰C] [16kW=2⁰C] [17kW=1⁰C] [25kW=0⁰C] [30kW= ]
PARAMETER: [P25] RANGE: -5 ~ 10⁰C RECOMMENDED SETTING:[8kW=2⁰C] [11kW=1⁰C] [16kW=4⁰C] [17kW=3⁰C] [25kW=1⁰C] [30kW= ]
PARAMETER: [P26] RANGE: [0]=Non Stop [1]=Reach Temp Stop [2]=Stop for 15 mins on 1 min after reach target temp. RECOMMENDED SETTING:[0] Non Stop is suitable for standard heat pump installation. [1] Temp Stop option can be used with buffer tank installation.
PARAMETER: [P47] RANGE: [0]=Not Valid [1]=Valid RECOMMENDED SETTING:[8kW=0] [11kW=0] [16kW=0] [17kW=0] [25kW=0] [30kW=0]
PARAMETER: [P50] RANGE: 3 ~ 60 L/min RECOMMENDED SETTING:[8kW=10] [11kW=15] [16kW=20] [17kW=20] [25kW=20] [30kW= ]
PARAMETER: [P52] RANGE: [0]=On/Off [1]=YF-G1 [2]=YF-DN50 RECOMMENDED SETTING:[8kW=1] [11kW=1] [16kW=1] [17kW=1] [25kW=2] [30kW= ]
INSTALLATION & FITTINGS
All air bled from system ?
Return water strainer fitted ?
ELECTRICAL READINGS
L1-N Reading
L2-N Reading
L3-N Reading
L1-N Reading
L2-N Reading
L3-N Reading
STATUS READING
To access status readings; Press both Mode[8] & Down▼[3] key together for 5 seconds. Press Down▼[3] and Up▲[4] key to scroll status codes and values. [code will flash then value] Once finished, press Power[10] to exit and return to home screen.
PARAMETER: [C2]
PARAMETER: [C3] PORT: [IN3]
PARAMETER: [C8] RECOMMENDED SETTING:[0]=DHW OFF [1]=DHW ON
PARAMETER: [C47] RECOMMENDED SETTING:L/min x 0.1
READING
CODE: [D20] LCD Reading PORT: [IN2]
CONTACT DETAILS
Clients Name
Clients Name
Date
Date